top of page
Website Banner for LW link on MOBILE B.png

The Total Weight Method

Updated: Mar 2

This charging method is used for systems that have no refrigerant. It is also used on new systems with a known amount of refrigerant in the outdoor unit. The goal is to break the vacuum with the exact amount of refrigerant needed for the system to function correctly. The amount of refrigerant needed can also be added after breaking the vacuum with refrigerant from the outdoor unit while the system is running.


If a new split system is being installed and the Total Weight Method is used, first view the rating plate of the outdoor unit and read the “factory charge”. This is the amount of refrigerant that comes with the outdoor unit and is locked inside the unit by the service valves.

Next, read the installation literature for the outdoor unit to determine if the factory charge includes a set amount of line set length (such as 15’ or 25’) the evaporator size, and the filter drier size. If the evaporator coil and filter drier match the size listed for the outdoor unit but the line set length is longer than the length included in the factory charge, add the additional refrigerant weight needed. If the actual length of line set is shorter than what is included in the factory charge then recover the amount of refrigerant needed from the system.


Refrigerant weight per foot can be determined using a manufacturer weight chart or the “Refrigerant Weight Per Foot” chart such as this below. Manufacturer charts supersede the chart below.

Example 1: A new R-410A split heat pump system is installed during the winter with 60’ of 7/8” vapor line and 60’ of 3/8” liquid line. The manufacturer’s factory charge of 8 lb 7 oz includes enough refrigerant for 15’ of 7/8” and 15’ of 3/8” line set. How much extra refrigerant needs to be added to the factory charge for an accurate system charge?


Steps to determine the Total Refrigerant Weight:

60’ - 15’ = 45’ of line set

For the 3/8” liquid line, add .54 oz per foot as seen in the “Refrigerant Weight Per Foot” chart.

45’ x .54 = 24.3 oz

For the 7/8” vapor line, add .153 oz per foot as seen in the “Refrigerant Weight Per Foot” chart.

45’ x .153 = 6.89 oz

24.3 + 6.89 = 31.19 oz of additional refrigerant needed


Example 2: A new R-410A split heat pump system is installed during the winter with 40’ of 3/4” vapor line and 40’ of 3/8” liquid line. The manufacturer’s factory charge of 6 lb 5 oz includes enough refrigerant for 15’ of 3/4” and 15’ of 3/8” line set. How much extra refrigerant needs to be added to the factory charge for an accurate system charge?


Steps to determine the Total Refrigerant Weight:

40’- 15’ = 25’ of line set

For the 3/8” liquid line, add .54 oz per foot as seen in the “Refrigerant Weight Per Foot” chart.

25’ x .54 = 13.5 oz

For the 3/4” vapor line, add .114 oz per foot as seen in the “Refrigerant Weight Per Foot” chart.

25’ x .114 = 2.85 oz

13.5 + 2.85 = 16.35 oz of additional refrigerant needed


Example 3: An old R-22 packaged unit had a refrigerant leak and leaked all of the refrigerant out. The leak was fixed and the unit was pressure tested and then vacuumed. The rating plate states a factory charge of 6 lb 5.8 oz. This is the exact amount of refrigerant that the unit needs to have weighed in. The vacuum can be broken with the full amount of refrigerant weighed in as a liquid into the liquid line.


Breaking the vacuum with refrigerant from the bottle is explained in this video- https://youtu.be/RA7BY7dixIg



Check out our book “Refrigerant Charging and Service Procedures for Air Conditioning”.

The full outline is available at https://www.acservicetech.com/the-book

If you have already purchased our book, be sure to tell local HVACR Instructors about our book and what you think of it. We would love to get the book into the hands of the next generation of HVACR Technicians!

Published: 4/15/2019

Author: Craig Migliaccio

About the Author:Craig is the owner of AC Service Tech LLC and the Author of the book “Refrigerant Charging and Service Procedures for Air Conditioning”. Craig is a licensed Teacher of HVACR, Sheet Metal, and Building Maintenance in the State of New Jersey of the USA. He is also an HVACR Contracting Business owner of 15 years and holds an NJ HVACR Master License. Craig creates educational HVACR articles and videos which are posted at https://www.acservicetech.com & https://www.youtube.com/acservicetechchannel

11 Comments


mark henry
mark henry
19 hours ago
  1. I found this article on pm kisan yojana very helpful. You have covered all the important aspects, including registration and benefits, which makes it a complete guide for farmers.

Like

mark henry
mark henry
19 hours ago
  1. I really liked your explanation of School Education Portal 3.0. The content is very detailed and written in a simple language, which helps users easily understand how to use the portal for school-related tasks.

Like

deepika.p
a day ago

I found this informative post about the total weight method to be very useful for my current study on sports science. The details are shared in an easy format to follow. (Dmwin Login)

Like

deepika.p
a day ago

This guide makes the details of volume management and recovery look very easy to follow for all lifters. I appreciate the effort put into organizing the information so clearly. (Jalwa Game)

Like

deepika.p
a day ago

A very well-written post about why tracking total tonnage is the backbone of muscle hypertrophy and performance gains today. It’s rare to find such high-quality exercise analysis explained so simply. (Jaiclub Game)

Like
AccuTrak ad
danfoss ad
Asurity-Digital-Ads_High_Res_1080x360.jp
AC Service Tech Ad
Join Our Updates List!

AC Service Tech HVAC Training is made possible by continued support from our visitors, customers, and support from these Sponsors!

NAVAC LOGO Black_edited.png
Accutrak Logo
TruTech-Tools-Logo-Main (3)[528].png
HavenRGB-FC w_grey horz.png

AC SERVICE TECH, LLC

Updates List

Thanks for submitting!

Thanks for all your continued support! I appreciate all the comments, questions, and responses that I receive from each of you. I look forward to responding to many more! If you have an HVACR related question, drop it in the comment section of one of the YouTube videos at the AC Service Tech YouTube Channel and I will do my best to respond.

 

For business related inquires email us at info@acservicetech.com

Check back regularly as we are always updating and improving this website!

© 2026 AC Service Tech, LLC.

bottom of page