top of page
Website Banner for LW link on MOBILE B.png

Testing Capacitors

Updated: Mar 2

An HVACR capacitor can be tested after turning the power off, disconnecting the wiring, and bleeding off any leftover voltage before testing. This can be done with a multimeter on the uF or MFD setting.


On a run capacitor, most of the voltage will drain off from the capacitor during the off cycle of the motor. This is because the run capacitor is attached to the motor while it is still spinning after the voltage is shut off.


In the case of a start capacitor, the voltage will still be stored by the capacitor unless there is a bleed resistor permanently installed between the two terminals of the capacitor. If there is no bleed resistor, the start capacitor will store voltage because a component such as a potential relay, a PTC thermistor or a current starting relay has kicked the capacitor out of the electrical circuit during the first fraction of a second of run time while it still has voltage in it.


A run capacitor is usually round or oval and silver or gray but it can also be a rectangle shape and black. Start capacitors are typically round and black.



Capacitors can be visually checked prior to measuring for uF/mfd. The capacitor is known to be bad if it has one of the following visual clues:


1. dielectric fluid leaking out of the capacitor

2. the top cap on the capacitor is moist with oil

3. there is a mushrooming of the top cap of the capacitor

4. the capacitor body looks expanded


A capacitor can be bad even if it shows no obvious signs of a problem. To test a capacitor, turn off the power to the unit, note which terminals the wires are connected to, and disconnect the wires. Finish discharging the capacitor using a 10,000 to 20,000 ohm resistor across the terminals from C to Herm and C to Fan. (If the terminals are rusty, a file can be used to expose the bare metal at the contacts.) If a resistor is not available, the capacitor could be shorted by holding onto the plastic part of a screwdriver and place the unpainted metal edge of the screwdriver from the C to Herm and from the C to the Fan. If the capacitor is not a dual run capacitor with three taps then it is a standard single capacitor with only two taps. Simply place the resistor across the two taps to discharge the voltage. If the voltage is not discharged, the multi-meter will not be able to read the capacitance in uF MFD.

In order to determine if the capacitor is good, the uF MFD should be within 5 to 6% of the rated uF MFD storage capacity stamped on the side of the capacitor. If the capacitor is visually bad or if the measurements are outside of the 5 to 6% of the rated capacitance, the capacitor should be replaced. The capacitor should be replaced with a new one that has the exact same uF MFD rating as the old one. The voltage rating must be the same or higher than the old one.


If the capacitor ratings are worn off of the old capacitor, look for a uF MFD rating on the side of the condenser fan and the compressor.


The compressor is always higher than the fan MFD. To measure the herm part of the capacitor, place one multimeter probe on the C terminal and one probe of the Herm terminal. Wait ten seconds for an accurate reading. To measure the Fan part of the capacitor, place one probe on the Fan terminal and the other probe on the C terminal. If the capacitor is just a single capacitor then there are only two terminals. It doesn’t matter which probe is placed on what terminal. Also when wiring back in the new capacitor, it doesn’t which side of the capacitor is the inlet and which one is the outlet voltage.


To learn more about HVACR capacitors, view these videos-



Check out our book “Refrigerant Charging and Service Procedures for Air Conditioning”.

The full outline is available at https://www.acservicetech.com/the-book

If you have already purchased our book, be sure to tell local HVACR Instructors about our book and what you think of it. We would love to get the book into the hands of the next generation of HVACR Technicians!

Published: 4/18/2019

Author: Craig Migliaccio

About the Author: Craig is the owner of AC Service Tech LLC and the Author of the book “Refrigerant Charging and Service Procedures for Air Conditioning”. Craig is a licensed Teacher of HVACR, Sheet Metal, and Building Maintenance in the State of New Jersey of the USA. He is also an HVACR Contracting Business owner of 15 years and holds an NJ HVACR Master License. Craig creates educational HVACR articles and videos which are posted at https://www.acservicetech.com & https://www.youtube.com/acservicetechchannel

17 Comments


Panther Jain
Panther Jain
5 days ago

I installed this game recently just to explore something new, and the experience has been quite smooth so far. The interface is simple and clearly designed, which makes navigation very easy for new users. I didn’t experience any lag or technical issues during gameplay. Everything runs properly and feels stable. The gameplay is relaxed and comfortable, which makes it enjoyable for casual sessions. Overall, it’s a good option for anyone who prefers simple games and wants something easy to play in their free time.

TC Lottery download

Like

The emphasis on accurate uF measurement and staying within tolerance is something many people underestimate, but it’s critical for system performance. Balancing technical learning with short mental breaks, like a quick run in Subway Surfers City, actually helps me retain information better—would you recommend any specific practice routine for mastering capacitor diagnostics?

Edited
Like

Tối qua mình đọc các bình luận trao đổi trên một diễn đàn, mình bắt gặp https://KP88S.COM  được chèn vào giữa câu chuyện. Mình bấm thử xem cho biết, chủ yếu là để xem cách trình bày và cấu trúc nội dung. Lướt nhanh thì thấy tổng thể khá gọn gàng, tạo cảm giác đáng tin cậy. Xem xong mình quay lại đọc tiếp các bình luận khác, chứ cũng không đào sâu thêm

Like

Tối qua mình đọc các bình luận trao đổi trên một diễn đàn, mình bắt gặp https://tr88s.net/  được chèn vào giữa câu chuyện. Mình bấm thử xem cho biết, chủ yếu là để xem cách trình bày và cấu trúc nội dung. Lướt nhanh thì thấy tổng thể khá gọn gàng, tạo cảm giác đáng tin cậy. Xem xong mình quay lại đọc tiếp các bình luận khác, chứ cũng không đào sâu thêm

Like

Hôm nọ mình có đọc qua một số bài viết trên mạng và thấy mọi người nhắc đến GO99, nên mình cũng hơi hiếu kỳ mở ra xem thử. Mặc dù không tìm hiểu kỹ lắm, nhưng mình chỉ lướt qua để xem bố cục và cách trình bày nội dung. Cảm giác cũng khá ổn, dễ nhìn và dễ hiểu, nên sau đó mình lại quay lại theo dõi các bình luận khác.

Like
AccuTrak ad
danfoss ad
Asurity-Digital-Ads_High_Res_1080x360.jp
AC Service Tech Ad
Join Our Updates List!

AC Service Tech HVAC Training is made possible by continued support from our visitors, customers, and support from these Sponsors!

NAVAC LOGO Black_edited.png
Accutrak Logo
TruTech-Tools-Logo-Main (3)[528].png
HavenRGB-FC w_grey horz.png

AC SERVICE TECH, LLC

Updates List

Thanks for submitting!

Thanks for all your continued support! I appreciate all the comments, questions, and responses that I receive from each of you. I look forward to responding to many more! If you have an HVACR related question, drop it in the comment section of one of the YouTube videos at the AC Service Tech YouTube Channel and I will do my best to respond.

 

For business related inquires email us at info@acservicetech.com

Check back regularly as we are always updating and improving this website!

© 2026 AC Service Tech, LLC.

bottom of page