How to Tell if a TXV Has Lost Part of its Bulb Charge! (Quick Tip)

Updated: Mar 2


How do you tell if a TXV lost part of its bulb charge? If you are measuring a correct/high subcooling along with a high superheat and a low saturated temperature on the vapor line, there may be a liquid line restriction!


Usually when a TXV bulb looses its bulb charge, it looses it slowly. One of the most obvious visual signs that a TXV has lost its bulb charge is if the top of the txv is very rusted. That would be the leak point of the refrigerant.


If you are measuring a high superheat and are just not sure if the bulb is the culprit, you could try taking the bulb off of the vapor line and putting it in hot water. If suddenly the vapor pressure rises and the superheat lowers then this tells you that bulb is partially low on refrigerant but there is still enough refrigerant to push down on the head of the TXV. When the bulb pressure pushes down on the head of the TXV, it opens the orifice inside the TXV a bit and allows more refrigerant into the evaporator.


Remember that if the vapor pressure does not rise and the superheat does not lower, it may be a problem other than the TXV or it may be that the TXV bulb has leaked out all its pressure. The problem could also be the strainer screen or the filter drier. Usually, the first thing to check for when assuming there is a liquid line restriction is the filter drier. This can be checked by measuring if there is a temp drop across the drier. There should not really be any temp drop. If there is a significant drop, it is due to a restriction and pressure drop. Have fun HVACing!


Check out our New Quizzes! https://www.acservicetech.com/quizzes

Best Wishes, Craig Migliaccio

8 Comments


I really like how you explained the three forces acting on the TXV; it helps me understand the mechanism much better. I was playing Drift Boss but this post was so good I had to stop and read it thoroughly great field knowledge!

Like

Bros Kart
Bros Kart
Apr 09

kart bros is a racing game that offers a diverse array of levels and obstacles, enabling players to refine their driving skills and strategies. In order to obtain high scores, players have the ability to create their own tracks, experiment with acceleration timing, and master the precise moments to clear obstacles. The application of in-game tips and hints improves the overall experience and the ability to complete laps efficiently, providing both excitement and the motivation to surmount every challenge.

Like

Online dolls have transformed how people interact with creativity and imagination in digital spaces. These virtual figures allow users to customize outfits, styles, and personalities with ease. Many platforms offer engaging features, helping users design unique characters and share them with friends. Visiting the official page often provides access to new updates, themes, and tools. From casual entertainment to creative expression, online dolls continue to attract users of all ages. This growing trend highlights how technology can turn simple ideas into interactive and enjoyable experiences for modern audiences worldwide.

Like

Usually when a Smash Karts bulb looses its bulb charge, it looses it slowly. One of the most obvious visual signs that a TXV has lost its bulb charge is if the top of the txv is very rusted. That would be the leak point of the refrigerant.

Edited
Like

Music becomes pure fun in Friday Night Funkin game, where I love testing my reflexes, matching arrows to beats, and feeling proud each time a difficult song finally clicks.

Like
AccuTrak ad
danfoss ad
Asurity-Digital-Ads_High_Res_1080x360.jp
AC Service Tech Ad
Join Our Updates List!

AC Service Tech HVAC Training is made possible by continued support from our visitors, customers, and support from these Sponsors!

NAVAC LOGO Black_edited.png
Accutrak Logo
TruTech-Tools-Logo-Main (3)[528].png
HavenRGB-FC w_grey horz.png

AC SERVICE TECH, LLC

Updates List

Thanks for submitting!

Thanks for all your continued support! I appreciate all the comments, questions, and responses that I receive from each of you. I look forward to responding to many more! If you have an HVACR related question, drop it in the comment section of one of the YouTube videos at the AC Service Tech YouTube Channel and I will do my best to respond.

 

For business related inquires email us at info@acservicetech.com

Check back regularly as we are always updating and improving this website!

© 2026 AC Service Tech, LLC.

bottom of page