Why Do Some Evap Coils Leak While Others Do Not? (Quick Tip)

Updated: Jul 13, 2023


ree

Why do older coils seem to last a long time but ones that are only 10 or 15 years old leak? Energy transfer efficiency was not as much of a concern on older equipment and the tubing used in these older coils had a thicker outside wall dimension. On newer coils made over the last 20 years, the tubing in the coil is thinner, and in most cases, they have an increased surface area on the inside for quick heat transfer. The picture shows this increased surface area.

The problem is, the coils don’t seem to last as long when they have thinner outside walls especially on coils that have a galvanized tin plate on the sides of coil. This galvanized plate rusts and the reaction with the tubing creates leaks where the copper tube elbows are. We are now finding leaks on the tubing in the middle of the coil, leaks where the rusted tin meets the elbows, and leaks due to bad swaging and minimal braze joint coverage.


Be sure to check out our video on Where to Find R-22 & R-410A LEAKS on AC Units!

9 Comments


Zumlar
Zumlar
Nov 21

Makes sense - newer coils are built for efficiency, not longevity. Thinner tubing and more surface area improve heat transfer but also make them more prone to leaks, especially where copper meets galvanized tin or at braze joints. Sometimes older, thicker-walled coils just outlast newer designs because they were built tougher, even if less efficient.

Like

John Corley
John Corley
Sep 21, 2023

That was one of the first things I was taught in plumbing, two dissimilar metals touching each other creates electrolysis. That's why they use brass and dielectric unions.

Like
Replying to

Not all dissimilar metals contact that create chemical reaction, however Aluminum with most metals cause chemical reaction, hence Aluminum ladders are not allowed in hazardous(classified zone 0 or 1) locations, elevated temperature environments as in coils catalyzes the reactions.

Like

John S.
John S.
Sep 20, 2023

Please do some videos on troubleshooting heat pumps. Specifically how to troubleshoot bad defrost board, and issues with defrost. Heating season is coming. Would be perfect.

Like

John S.
John S.
Sep 20, 2023

I purchased you complete set of Air Conditioning books w/ the E book included when I was in school. I was so far ahead of everyone else because I studied this book over and over.

Like

D_H_Gore
Aug 03, 2023

It would be interesting to know how much thicker the older coils were. X2, X4 ? Bet it is a lot. Would like to see a picture of an old coil cut apart. I did buy your book. Good book.

Like
John S.
John S.
Sep 20, 2023
Replying to

I would like to see a side by side comparison, as well.

Like
AccuTrak ad
danfoss ad
Asurity-Digital-Ads_High_Res_1080x360.jp
AC Service Tech Ad
Join Our Updates List!

AC Service Tech HVAC Training is made possible by continued support from our visitors, customers, and support from these Sponsors!

NAVAC LOGO Black_edited.png
Accutrak Logo
TruTech-Tools-Logo-Main (3)[528].png
HavenRGB-FC w_grey horz.png

AC SERVICE TECH, LLC

Updates List

Thanks for submitting!

Thanks for all your continued support! I appreciate all the comments, questions, and responses that I receive from each of you. I look forward to responding to many more! If you have an HVACR related question, drop it in the comment section of one of the YouTube videos at the AC Service Tech YouTube Channel and I will do my best to respond.

 

For business related inquires email us at info@acservicetech.com

Check back regularly as we are always updating and improving this website!

© 2025 AC Service Tech, LLC.

bottom of page