top of page
Slide for homepage w stroke.jpg

Measuring Airflow in CFM Using the TrueFlow Grid

Updated: Feb 24

Measuring airflow is one of the most commonly missed or ignored topics in HVAC when commissioning or diagnosing problems in systems. I don't believe this topic is purposely ignored due to lazyness or just wanting to reduce the time on service calls. I believe it actually stems from the lack of easy to follow methods, and a lack of accuracy in some methods due to either system design or tool limitations.


ree

Below are possible methods or tools to measure airflow in HVAC systems:

  • Temp Rise Formula

  • Measuring TESP and comparing to manufacturer's data

  • Hot Wire Anemometer

  • Rotating Vane Anemometer

  • Timed Inflation

  • Flow Capture Hood

  • Traversing the Duct

  • TEC TrueFlow Grid


Indoor airflow should be measured to ensure that enough air is constantly being carried through the HVAC system to absorb or reject heat. Poor airflow can lead to multiple different issues, including a gas furnace overheating, a frozen evaporator coil on an air conditioner, high pressure limit tripping on a heat pump in heating mode, as well as a general lack in energy efficiency and comfort. In this article, we will be covering one of my favorite methods to measure airflow.


We will be discussing the steps to use the TEC TrueFlow Grid. The Digital TrueFlow Grid kit includes the Digital TrueFlow Grid, DG-8 pressure gauge, a magnetic static pressure probe, and eight TrueFlow adapter plates in varying sizes. If you are looking for this kit, it is available here.


To begin this method, you will need to determine the TrueFlow adapter size that fits your system. The selected adapter should have the same measurements as the filter inside the system. You will also need your Digital Trueflow Grid, DG-8 Digital Pressure Gauge or the DG-100 Digital Pressure and Flow Gauge, and your phone or tablet with the TrueFlow app downloaded.

ree

The TrueFlow app will allow you to read the information the kit provides. If you haven’t already, you will first need to download the free TrueFlow app onto your phone or tablet.


Step 1: Connect the Devices

To connect the devices you will be using with the app, power on the Digital Pressure Gauge and the TrueFlow Grid. Make sure that your phone or tablet’s Bluetooth is on, and select both the Pressure Gauge and TrueFlow Grid as devices on the app to connect them. Connected devices should appear as shown below:

ree

Step 2: Set up the Workflow

You will need to select a workflow for the system you are testing. To measure airflow, select the System Air Flow option, under the Measurement tab. Next select either Furnace or Air Handler. In our case, we will select Furnace. Then choose your system’s airflow orientation: Upflow, Downflow, or Horizontal. In our case, we will select Upflow.

ree

Step 3: Enter the System's BTU/HR Capacity

In our case, we will be measuring air conditioning capacity. To find the unit's BTU/HR size, we can look at the outdoor unit's rating plate. In our case, the unit has 24,000 BTU/hr of heat removal capacity, which calculates to 2 tons. For reference, 12,000 BTU/HR = 1 ton of heat removal capacity. Enter the unit’s cooling capacity in tons within the app.

ree

Step 4: Selecting the Air Filter Location

Select the location of the system's air filter. In our case, the air filter is in the filter slot within the duct or cabinet, next to the furnace. If you’re measuring a system's central Filter Return Air Grille (FRAG), select this instead. If there are multiple FRAGs, take a reading from the biggest one and temporarily close off the other smaller ones.

ree

Step 5: Insert the Static Pressure Tip

Use a step bit to create a small 3/8"hole in the supply plenum immediately downstream of the unit. Insert the static pressure tip with the point in the direction in which the airflow will be coming from. In our case, because we are measuring an upflow system, the point will be faced downward. (After taking the readings, a duct plug can be used to cover the hole.)

ree

ree

Step 6: Take the First Measurement

To begin the first reading, leave the existing (new) filter in the system. Turn the system on in air conditioning mode and let the system’s blower motor get up to full speed. Once the system is up to speed, press the Take Measurement option on your app. In order to avoid cycling on and off the system's compressor, the outdoor disconnect can be turned to the off position. This will result in the evaporator coil being dry during your measurements instead of wet. This will be discussed more in Step 9.

ree

Step 7: Turn the System Off and Insert the TrueFlow Grid

Once the first scan is complete, turn off the system and remove the air filter. Then you can insert the adapter with the TrueFlow Grid into the filter cabinet and close the door. (If you selected the FRAG, you would be putting the TrueFlow Grid in that location instead.)

ree

Step 8: Take the Second Measurement

Leave the static pressure tip in the previous location and turn the system on in air conditioning mode. Again, let the system get up to full airflow speed. Press the Take Measurement option, this time with the TrueFlow Grid rather than the filter. During this test, the static pressure will provide the correction factor for the difference between the TrueFlow Grid and the air filter.

ree

Step 9: Results

Once this scan completes, the app will display the actual airflow measurement in CFM for the system. A decent airflow number is between 350-450 CFM per ton, depending on your desired dehumidification, during air conditioning mode. Dry climates can have 450-425 CFM while moist climates may require 350-375 CFM in order to have effective humidity removal.

ree

If low airflow is recorded, the next step is to determine if there is a restriction in the ductwork in either the return or supply. The workflow System Airflow & Static Pressure can be followed to help determine the location of the problem. It is possible that there is no problem and the airflow speed within the unit just needs to be adjusted.


Remember that this procedure was done with the outdoor unit off. This means that there was a dry evaporator coil, which results in a lower static pressure drop across the coil and a higher airflow measured than that which it will be running with during air conditioning mode. If you want to have a wet coil during these tests (which results in a more accurate measurement), the power would have to remain on at the indoor and outdoor units while replacing the filter with the TrueFlow grid at the filter cabinet during the tests. Make sure to recover your TrueFlow grid after your test and put the air filter back in its place after testing.


If you would like to watch a full video on this subject, click here:


If you are interested in learning more about how to find airflow problems using static pressure measurements, check out this article here: https://www.acservicetech.com/post/finding-an-airflow-problem-using-static-pressure-measurements


Tools Used


ree



Published: 12/13/2023 Author: Craig Migliaccio

ree

About the Author: Craig is the owner of AC Service Tech LLC and the Author of the book “Refrigerant Charging and Service Procedures for Air Conditioning”. Craig is a licensed Teacher of HVACR, Sheet Metal, and Building Maintenance in the State of New Jersey of the USA. He is also an HVACR Contracting Business owner of 15 years and holds an NJ HVACR Master License. Craig creates educational HVACR articles and videos which are posted at https://www.acservicetech.com & https://www.youtube.com/acservicetechchannel


2 Comments


Citation from panasonic reviews additionally, the sleek design of the appliances adds a modern touch to my home, making them not only practical but also aesthetically pleasing. Overall, I highly recommend Panasonic for anyone seeking durable and high-performing electronics. I purchased several Panasonic appliances and electronics, and my experience has been overwhelmingly positive. The quality of the products is exceptional, with a user-friendly interface that enhances functionality. Each device operates efficiently, delivering reliable performance that meets my expectations.

Edited
Like

wrighttchristian
Jul 02, 2024

An HVAC Contractor measures airflow using tools like anemometers, manometers, and flow hoods. They assess air velocity and volume to ensure proper system performance. Accurate airflow measurement helps in diagnosing issues, optimizing efficiency, and ensuring even temperature distribution. Regular checks by an HVAC contractor keep your system running smoothly.

Like
AccuTrak ad
danfoss ad
Asurity-Digital-Ads_High_Res_1080x360.jp
AC Service Tech Ad
Join Our Updates List!

AC Service Tech HVAC Training is made possible by continued support from our visitors, customers, and support from these Sponsors!

NAVAC LOGO Black_edited.png
Accutrak Logo
TruTech-Tools-Logo-Main (3)[528].png
HavenRGB-FC w_grey horz.png

AC SERVICE TECH, LLC

Updates List

Thanks for submitting!

Thanks for all your continued support! I appreciate all the comments, questions, and responses that I receive from each of you. I look forward to responding to many more! If you have an HVACR related question, drop it in the comment section of one of the YouTube videos at the AC Service Tech YouTube Channel and I will do my best to respond.

 

For business related inquires email us at info@acservicetech.com

Check back regularly as we are always updating and improving this website!

© 2025 AC Service Tech, LLC.

bottom of page