How to Tell if a TXV Has Lost Part of its Bulb Charge! (Quick Tip)

Updated: Jul 13, 2023


ree

How do you tell if a TXV lost part of its bulb charge? If you are measuring a correct/high subcooling along with a high superheat and a low saturated temperature on the vapor line, there may be a liquid line restriction!


Usually when a TXV bulb looses its bulb charge, it looses it slowly. One of the most obvious visual signs that a TXV has lost its bulb charge is if the top of the txv is very rusted. That would be the leak point of the refrigerant.


If you are measuring a high superheat and are just not sure if the bulb is the culprit, you could try taking the bulb off of the vapor line and putting it in hot water. If suddenly the vapor pressure rises and the superheat lowers then this tells you that bulb is partially low on refrigerant but there is still enough refrigerant to push down on the head of the TXV. When the bulb pressure pushes down on the head of the TXV, it opens the orifice inside the TXV a bit and allows more refrigerant into the evaporator.


Remember that if the vapor pressure does not rise and the superheat does not lower, it may be a problem other than the TXV or it may be that the TXV bulb has leaked out all its pressure. The problem could also be the strainer screen or the filter drier. Usually, the first thing to check for when assuming there is a liquid line restriction is the filter drier. This can be checked by measuring if there is a temp drop across the drier. There should not really be any temp drop. If there is a significant drop, it is due to a restriction and pressure drop. Have fun HVACing!

Check out our New Quizzes! https://www.acservicetech.com/quizzes

Best Wishes, Craig Migliaccio

2 Comments


ron.suerecord
ron.suerecord
Nov 01, 2023

Why are most residential TXVs non adjustable? Do you think that EEVs will eventually replace TXVs in residential and light commercial applications?

Like

akeem ajayi
akeem ajayi
Jan 02, 2023

Can I be tired of reading this article? NO...NO... NO... Really appreciate

Like
AccuTrak ad
danfoss ad
Asurity-Digital-Ads_High_Res_1080x360.jp
AC Service Tech Ad
Join Our Updates List!

AC Service Tech HVAC Training is made possible by continued support from our visitors, customers, and support from these Sponsors!

NAVAC LOGO Black_edited.png
Accutrak Logo
TruTech-Tools-Logo-Main (3)[528].png
HavenRGB-FC w_grey horz.png

AC SERVICE TECH, LLC

Updates List

Thanks for submitting!

Thanks for all your continued support! I appreciate all the comments, questions, and responses that I receive from each of you. I look forward to responding to many more! If you have an HVACR related question, drop it in the comment section of one of the YouTube videos at the AC Service Tech YouTube Channel and I will do my best to respond.

 

For business related inquires email us at info@acservicetech.com

Check back regularly as we are always updating and improving this website!

© 2025 AC Service Tech, LLC.

bottom of page