How to Find Common, Start, and Run on a PSC Compressor Motor!
- Craig Migliacco

- Apr 28, 2021
- 4 min read
Updated: Feb 25

In this HVACR Training article, we are using electrical resistance measurements on the PSC compressor terminals in order to determine which tab is Common, Start, and Run. This is used when the tabs are not labeled, there is no plug for the terminals, or there is no electrical wiring diagram available for the wires feeding from the terminals.
The steps listed below can be used to test all single speed PSC motors (i.e., compressors, blower motors). Whenever possible, first measure the electrical resistance via the wires connected to the compressor tabs. This can be done by first removing the compressor wires from the contactor and the capacitor and testing the wires there in the electrical compartment. If that is not giving a proper resistance value, then move to the compressor itself and disconnect the wires from the compressor tabs to take the measurements there. Take precaution any time the wires need to be removed from the compressor terminals because refrigerant pressure is being held back via the Fusite glass and terminals.

To test these motors, we will be using a multimeter. To get started, set the multimeter to ohms (Ω). This setting allows us to test for electrical resistance. Test your meter for accuracy before taking measurements. When the meter probes are not touching, the meter should display OL. When the meter probes are touching, the meter should display 0.0 ohms. Before testing the compressor motor, make sure the power is off to the unit and compressor.
Step 1: Check Resistance Values

A) Connect the alligator clips to terminal pairs in order to check the resistance value of each pair.
B) Gather resistance values and mark which pairs provided each reading.

In our example above, we can see that the resistance measurement between the top and bottom right terminal is 1.5 ohms. The measurement between the bottom two terminals is 7.5 ohms. The measurement between the top and bottom left terminal is 6 ohms. The highest measurement should equal the sum of both of the two lesser measurements.
7.5 = 6 +1.5
(Drawing a diagram for yourself, such as the one above, will make identifying each tab easier in the next step.)
Step 2: Identify Each Terminal
A) Identify the pair with the lowest resistance reading. This pair is always the Common and Run. This pair measured 1.5 ohms. This means that the other remaining tab is Start.
B) Identify the second highest resistance reading. This pair is always the Common and Start. This pair measured 6 ohms. This means that the other remaining tab is Run.
C) Identify the highest resistance reading. This pair is always the Start and Run. This pair measured 7.5 ohms. This means that the other remaining tab is Common.

In this way, you can always determine which tab is Common, Start, and Run. Just find the pair with the lowest resistance measurement. The remaining tab that is not in the pair is Start. You could also just find the pair with the highest resistance measurement. The remaining tab outside of the pair is the Common.
1.5 ohms (Common to Run) + 6 ohms (Common to Start) = 7.5 ohms (Start to Run)
Step 3: Determine if the Compressor has been Shorted to Ground.
When the three windings match up, as they do in our example, this would indicate there is no short. However, it is still a good idea to complete the following step.

A) Clip one alligator clip to one of the terminals.
B) Press the other probe onto a cleaned section of the copper tubing or unpainted steel on the compressor.
C) If the compressor is NOT shorted to ground, the multimeter will read OL.
At this point, you can be confident that the compressor is not shorted to ground and you know what terminals are what. If you need to do a deeper dive into the windings, a megger test would be needed.
If you are looking for a video to better help understand this topic, check out our "How to Find Common, Start, and Run on a PSC Compressor Motor!" video below!
If you want to learn about refrigerants and how they work in a system, check out our “Refrigerant Charging and Service Procedures for Air Conditioning” book . Test your knowledge with our 1,000 question workbook along with the answer key! We also have quick reference cards for use out in the field! Bundle Packs are a great way to save and get faster shipping! Check out www.acservicetech.com/store
Check out our free Quizzes to test your knowledge here!
Check out our Free Calculators here!
Tools that we use: www.amazon.com/shop/acservicetech
Published: 04/28/2021 Author: Craig Migliaccio

About the Author: Craig is the owner of AC Service Tech LLC and the Author of the book “Refrigerant Charging and Service Procedures for Air Conditioning”. Craig is a licensed Teacher of HVACR, Sheet Metal, and Building Maintenance in the State of New Jersey of the USA. He is also an HVACR Contracting Business owner of 16 years and holds an NJ HVACR Master License. Craig creates educational HVACR articles and videos which are posted at https://www.acservicetech.com & https://www.youtube.com/acservicetechchannel & https://www.facebook.com/acservicetech/










.png)








想要提升你的Instagram粉丝和点赞吗?ins买粉平台真正的互动和内容!💪✨ Instagram买粉丝你准备好迎接挑战了吗?在评论区告诉我们你的看法! #社交媒体 #真实连接
ins买粉平台 ins刷粉平台 购买Instagram粉丝 Instagram买点赞 Instagram买粉丝 Ins买粉 Ins买赞
https://inleo.io/threads/view/insshuafen/re-leothreads-2jmshdgca?referral=insshuafen
https://ideaexpress.us/%e5%9c%a8ins%e4%b9%b0%e7%b2%89%e5%b9%b3%e5%8f%b0%e4%b8%8a%e5%bf%ab%e9%80%9f%e5%a2%9e%e5%8a%a0%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e7%9a%84%e6%8a%80%e5%b7%a7/
https://ideaexpress.us/%e7%a7%b0%e9%9c%b8-instagram-%e7%9a%84%e7%ad%96%e7%95%a5%ef%bc%9a%e5%a2%9e%e5%8a%a0%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e4%bb%a5%e8%8e%b7%e5%be%97%e6%9b%b4%e5%a5%bd%e7%9a%84%e6%9b%9d%e5%85%89/
https://theblogyfi.com/%e9%80%9a%e8%bf%87ins%e5%88%b7%e7%b2%89%e5%b9%b3%e5%8f%b0%ef%bc%9ains%e4%b9%b0%e7%b2%89%e5%92%8cins%e4%b9%b0%e8%b5%9e/
https://nichenest.xyz/ins%e5%88%b7%e7%b2%89%e3%80%81ins%e5%88%b7%e8%b5%9e%e3%80%81%e6%8f%90%e5%8d%87instagram%e7%b2%89%e4%b8%9d%e3%80%81%e7%82%b9%e8%b5%9e%e3%80%81%e8%a7%82%e7%9c%8b%e9%87%8f%e4%b8%8e%e6%94%b6%e8%97%8f/
https://piventa.com/instagram%e5%a2%9e%e5%8a%a0%e6%92%ad%e6%94%be%e9%87%8f%e7%b2%89%e4%b8%9d%e7%82%b9%e8%b5%9e%ef%bc%8c%e6%8f%90%e9%ab%98%e8%b4%a6%e5%8f%b7%e6%8e%92%e5%90%8d/
https://discoverydell.com/%e6%8f%90%e5%8d%87-instagram%e6%b5%8f%e8%a7%88%e9%87%8f%e3%80%81%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e6%95%b0%e4%bb%a5%e6%8f%90%e5%8d%87%e8%b4%a6%e6%88%b7%e6%8e%92%e5%90%8d%e7%9a%84%e7%bb%88/
https://geniusvision.world/%e6%8f%90%e5%8d%87%e6%82%a8%e7%9a%84%e5%b8%90%e6%88%b7%ef%bc%9a%e5%a2%9e%e5%8a%a0-instagram-%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e7%9a%84%e6%9c%89%e6%95%88%e6%8a%80%e5%b7%a7/
https://bcrelx.com/ins%e5%88%b7%e7%b2%89%e3%80%81ins%e4%b9%b0%e7%b2%89%e3%80%81ins%e4%b9%b0%e8%b5%9e%e3%80%81ins%e5%88%b7%e8%b5%9e%e3%80%81instagram%e5%88%b7%e7%b2%89%e3%80%81instagram%e4%b9%b0%e7%b2%89%e3%80%81instagra/
https://topicterritory.com/tiktok%e5%8a%a0%e7%b2%89%e4%b8%9d%e7%82%b9%e8%b5%9e%e6%92%ad%e6%94%be%e9%87%8f%ef%bc%8c%e5%bf%ab%e9%80%9f%e6%8f%90%e9%ab%98%e6%8e%92%e5%90%8d/
https://inspirejournal.xyz/tk%e4%b9%b0%e7%b2%89%e3%80%81tk%e4%b9%b0%e8%b5%9e%e3%80%81tk%e5%88%b7%e7%b2%89%e5%b9%b3%e5%8f%b0%e3%80%81%e6%8f%90%e5%8d%87%e8%87%aa%e5%b7%b1%e7%9a%84%e7%b2%89%e4%b8%9d%e6%95%b0%e9%87%8f%e3%80%81/
https://inspirejournal.xyz/tiktok%e5%8a%a0%e7%b2%89%e4%b8%9d%e7%82%b9%e8%b5%9e%e6%92%ad%e6%94%be%e9%87%8f%ef%bc%8c%e6%98%af%e5%90%a6%e8%83%bd%e5%bf%ab%e9%80%9f%e6%8e%92%e5%90%8d/
https://ideaepic.com/tiktok%e5%88%b7%e7%b2%89%e7%ae%97%e6%b3%95%ef%bc%9a%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e8%b6%8a%e5%a4%9a%e6%8e%92%e5%90%8d%e8%b6%8a%e9%ab%98%e5%90%97/
https://trendburst.us/tiktok%e5%88%b7%e7%b2%89%e3%80%81tiktok%e4%b9%b0%e7%b2%89%e3%80%81tiktok%e5%88%b7%e8%b5%9e%e3%80%81tiktok%e4%b9%b0%e8%b5%9e%e3%80%81tiktok%e5%88%b7%e6%92%ad%e6%94%be%e9%87%8f%e3%80%81tk%e5%88%b7/
https://ideaexpress.us/%e7%a7%b0%e9%9c%b8-instagram-%e7%9a%84%e7%ad%96%e7%95%a5%ef%bc%9a%e5%a2%9e%e5%8a%a0%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e4%bb%a5%e8%8e%b7%e5%be%97%e6%9b%b4%e5%a5%bd%e7%9a%84%e6%9b%9d%e5%85%89/
https://trendtracker.us/%e6%8f%90%e5%8d%87%e6%82%a8%e7%9a%84fb%e6%8e%92%e5%90%8d%ef%bc%9afacebook%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e4%bc%98%e5%8c%96%e7%bb%88%e6%9e%81%e6%8c%87%e5%8d%97/
https://trendtracker.us/youtube%e5%8a%a0%e8%ae%a2%e9%98%85%e3%80%81%e6%92%ad%e6%94%be%e9%87%8f%e3%80%81%e7%82%b9%e8%b5%9e%e6%8f%90%e5%8d%87%e8%b4%a6%e5%8f%b7%e6%9d%83%e9%87%8d/
https://nichebase.xyz/%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e5%a2%9e%e9%95%bf%e5%af%b9-facebook-%e6%8e%92%e5%90%8d%e7%9a%84%e5%bd%b1%e5%93%8d%ef%bc%9a%e6%82%a8%e9%9c%80%e8%a6%81%e4%ba%86%e8%a7%a3%e7%9a%84%e5%86%85/
https://nichebase.xyz/%e8%a7%a3%e9%94%81-instagram-%e6%88%90%e5%8a%9f%e7%a7%98%e8%af%80%ef%bc%9a%e5%a6%82%e4%bd%95%e8%8e%b7%e5%be%97%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e5%b9%b6%e6%8f%90%e9%ab%98%e6%8e%92%e5%90%8d/
https://nichebase.xyz/%e5%be%81%e6%9c%8d-youtube-%e7%9a%84%e7%ad%96%e7%95%a5%ef%bc%9a%e9%80%9a%e8%bf%87youtube%e4%b9%b0%e7%b2%89%e3%80%81youtube%e4%b9%b0%e8%b5%9e%e3%80%81youtube%e4%b9%b0%e6%92%ad%e6%94%be%e9%87%8f/
https://1drv.ms/w/c/8231e311a5465d6d/EYjutBnV01FBmIGObk62P4IBHCcIPRz8amqjwjVEKbSzQg
https://mix.com/yun89087
https://logcla.com/yun89087
https://logcla.com/blogs/894090/TikTok%E5%88%B7%E6%92%AD%E6%94%BE%E9%87%8F%E5%92%8CTikTok%E5%88%B7%E7%82%B9%E8%B5%9E%E5%AF%B9%E6%8E%92%E5%90%8D%E6%9C%89%E5%B8%AE%E5%8A%A9%E5%90%97
https://bestbizportal.com/yun89087
https://berry.work/yun89087
http://bedfordfalls.live/yun89087
http://bedfordfalls.live/read-blog/182579_tk%E7%82%B9%E8%B5%9E%E5%92%8Ctk%E6%92%AD%E6%94%BE%E9%87%8F%E8%83%BD%E6%8F%90%E5%8D%87tiktok%E8%A7%86%E9%A2%91%E6%8E%92%E5%90%8D%E5%90%97.html
https://youslade.com/yun89087
https://likeminds.fun/yun89087
https://likeminds.fun/post/89768_tiktok%E7%82%B9%E8%B5%9E%E4%B8%8E%E8%A7%86%E9%A2%91%E6%92%AD%E6%94%BE%E9%87%8F%E5%AF%B9%E6%8E%92%E5%90%8D%E4%B9%8B%E9%97%B4%E7%9A%84%E5%85%B3%E7%B3%BB%E8%A7%A3%E6%9E%90-tiktok-tiktok%E5%88%B7%E7%B2%89-tiktok%E5%88%B7%E8%B5%9E.html
https://ayema.ng/fbfensicom
https://doorspell.com/fbfensicom
https://doorspell.com/blogs/51733/%E7%90%86%E8%A7%A3TikTok%E7%9A%84%E7%AE%97%E6%B3%95-%E7%B2%89%E4%B8%9D%E5%92%8C%E7%82%B9%E8%B5%9E%E8%B6%8A%E5%A4%9A%E6%8E%92%E5%90%8D%E8%B6%8A%E9%AB%98%E5%90%97
https://www.rugbynflforum.com/yun89087
https://www.rugbynflforum.com/read-blog/35889
https://localbizinfo.net/fbfensicom
https://localbizinfo.net/blogs/96296/%E4%BA%86%E8%A7%A3-TikTok-%E7%9A%84%E7%AE%97%E6%B3%95-TK%E5%88%B7%E6%92%AD%E6%94%BE%E5%92%8CTK%E5%88%B7%E8%B5%9E%E5%AF%B9%E5%86%85%E5%AE%B9%E6%8E%92%E5%90%8D%E7%9A%84%E5%BD%B1%E5%93%8D
https://nichenest.xyz/%e5%88%a9%e7%94%a8-ins%e4%b9%b0%e7%b2%89%e5%b9%b3%e5%8f%b0-%e4%bf%83%e8%bf%9binstagram%e7%b2%89%e4%b8%9d%e7%82%b9%e8%b5%9e%e6%92%ad%e6%94%be%e9%87%8f%e7%9a%84%e5%bf%ab%e9%80%9f%e5%a2%9e%e9%95%bf/
https://theblogyfi.com/ins%e5%88%b7%e7%b2%89%e5%b9%b3%e5%8f%b0%ef%bc%9a%e5%bf%ab%e9%80%9f%e5%a2%9e%e5%8a%a0%e7%b2%89%e4%b8%9d%e3%80%81%e7%82%b9%e8%b5%9e%e4%b8%8e%e6%92%ad%e6%94%be%e9%87%8f%e7%9a%84%e5%a4%9a%e7%a7%8d/
https://theblogyfi.com/ins%e5%88%b7%e7%b2%89%e5%b9%b3%e5%8f%b0%ef%bc%9a%e5%bf%ab%e9%80%9f%e5%a2%9e%e5%8a%a0%e7%b2%89%e4%b8%9d%e3%80%81%e7%82%b9%e8%b5%9e%e3%80%81%e6%92%ad%e6%94%be%e9%87%8f%e6%8f%90%e5%8d%87%e6%8e%92/
https://theblogyfi.com/%e4%ba%86%e8%a7%a3tiktok%e7%b2%89%e4%b8%9d%e5%af%b9%e8%b4%a6%e6%88%b7%e6%9d%83%e5%a8%81%e6%80%a7%e5%92%8c%e6%8e%92%e5%90%8d%e7%9a%84%e5%bd%b1%e5%93%8d/
https://theblogyfi.com/tk%e7%b2%89%e4%b8%9d-tk%e7%82%b9%e8%b5%9e%e6%95%b0%e9%87%8f%e8%b6%8a%e5%a4%9a%ef%bc%8ctiktok%e8%b4%a6%e6%88%b7%e6%9d%83%e9%87%8d%e8%b6%8a%e9%ab%98%e5%90%97%ef%bc%9f/
https://theblogyfi.com/instagram-tiktok-facebook-youtube-%e9%80%9a%e8%bf%87%e5%a2%9e%e5%8a%a0%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e8%8e%b7%e5%be%97%e6%8e%92%e5%90%8d/
https://indianwomenorg.com/yun89087
https://indianwomenorg.com/read-blog/36101
https://ideaexpress.us/youtube%e9%a2%91%e9%81%93%e8%ae%a2%e9%98%85%e5%92%8c%e7%82%b9%e8%b5%9e%e6%92%ad%e6%94%be%e5%af%b9%e6%8e%92%e5%90%8d%e6%9c%89%e4%bb%80%e4%b9%88%e5%bd%b1%e5%93%8d/
https://ideaexpress.us/%e5%a6%82%e4%bd%95%e6%9c%89%e6%95%88%e6%8f%90%e5%8d%87%e6%82%a8%e7%9a%84facebook%e5%bd%b1%e5%93%8d%e5%8a%9b/
https://ideaexpress.us/%e7%a7%b0%e9%9c%b8-instagram-%e7%9a%84%e7%ad%96%e7%95%a5%ef%bc%9a%e5%a2%9e%e5%8a%a0%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e4%bb%a5%e8%8e%b7%e5%be%97%e6%9b%b4%e5%a5%bd%e7%9a%84%e6%9b%9d%e5%85%89/
https://trendtracker.us/%e6%8f%90%e5%8d%87%e6%82%a8%e7%9a%84fb%e6%8e%92%e5%90%8d%ef%bc%9afacebook%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e4%bc%98%e5%8c%96%e7%bb%88%e6%9e%81%e6%8c%87%e5%8d%97/
https://trendtracker.us/youtube%e5%8a%a0%e8%ae%a2%e9%98%85%e3%80%81%e6%92%ad%e6%94%be%e9%87%8f%e3%80%81%e7%82%b9%e8%b5%9e%e6%8f%90%e5%8d%87%e8%b4%a6%e5%8f%b7%e6%9d%83%e9%87%8d/
https://nichebase.xyz/%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e5%a2%9e%e9%95%bf%e5%af%b9-facebook-%e6%8e%92%e5%90%8d%e7%9a%84%e5%bd%b1%e5%93%8d%ef%bc%9a%e6%82%a8%e9%9c%80%e8%a6%81%e4%ba%86%e8%a7%a3%e7%9a%84%e5%86%85/
https://nichebase.xyz/%e8%a7%a3%e9%94%81-instagram-%e6%88%90%e5%8a%9f%e7%a7%98%e8%af%80%ef%bc%9a%e5%a6%82%e4%bd%95%e8%8e%b7%e5%be%97%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e5%b9%b6%e6%8f%90%e9%ab%98%e6%8e%92%e5%90%8d/
https://nichebase.xyz/%e5%be%81%e6%9c%8d-youtube-%e7%9a%84%e7%ad%96%e7%95%a5%ef%bc%9a%e9%80%9a%e8%bf%87youtube%e4%b9%b0%e7%b2%89%e3%80%81youtube%e4%b9%b0%e8%b5%9e%e3%80%81youtube%e4%b9%b0%e6%92%ad%e6%94%be%e9%87%8f/
https://fbfensi.hashnode.dev/fbmaifensi
https://fbfensi.hashnode.dev/instagramshuafensi
https://fbfensi.hashnode.dev/youtubemaifensi
https://piventa.com/instagram%e5%a2%9e%e5%8a%a0%e6%92%ad%e6%94%be%e9%87%8f%e7%b2%89%e4%b8%9d%e7%82%b9%e8%b5%9e%ef%bc%8c%e6%8f%90%e9%ab%98%e8%b4%a6%e5%8f%b7%e6%8e%92%e5%90%8d/
https://discoverydell.com/%e6%8f%90%e5%8d%87-instagram%e6%b5%8f%e8%a7%88%e9%87%8f%e3%80%81%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e6%95%b0%e4%bb%a5%e6%8f%90%e5%8d%87%e8%b4%a6%e6%88%b7%e6%8e%92%e5%90%8d%e7%9a%84%e7%bb%88/
https://geniusvision.world/%e6%8f%90%e5%8d%87%e6%82%a8%e7%9a%84%e5%b8%90%e6%88%b7%ef%bc%9a%e5%a2%9e%e5%8a%a0-instagram-%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e7%9a%84%e6%9c%89%e6%95%88%e6%8a%80%e5%b7%a7/
https://bcrelx.com/ins%e5%88%b7%e7%b2%89%e3%80%81ins%e4%b9%b0%e7%b2%89%e3%80%81ins%e4%b9%b0%e8%b5%9e%e3%80%81ins%e5%88%b7%e8%b5%9e%e3%80%81instagram%e5%88%b7%e7%b2%89%e3%80%81instagram%e4%b9%b0%e7%b2%89%e3%80%81instagra/
https://topicterritory.com/tiktok%e5%8a%a0%e7%b2%89%e4%b8%9d%e7%82%b9%e8%b5%9e%e6%92%ad%e6%94%be%e9%87%8f%ef%bc%8c%e5%bf%ab%e9%80%9f%e6%8f%90%e9%ab%98%e6%8e%92%e5%90%8d/
https://inspirejournal.xyz/tk%e4%b9%b0%e7%b2%89%e3%80%81tk%e4%b9%b0%e8%b5%9e%e3%80%81tk%e5%88%b7%e7%b2%89%e5%b9%b3%e5%8f%b0%e3%80%81%e6%8f%90%e5%8d%87%e8%87%aa%e5%b7%b1%e7%9a%84%e7%b2%89%e4%b8%9d%e6%95%b0%e9%87%8f%e3%80%81/
https://inspirejournal.xyz/tiktok%e5%8a%a0%e7%b2%89%e4%b8%9d%e7%82%b9%e8%b5%9e%e6%92%ad%e6%94%be%e9%87%8f%ef%bc%8c%e6%98%af%e5%90%a6%e8%83%bd%e5%bf%ab%e9%80%9f%e6%8e%92%e5%90%8d/
https://ideaepic.com/tiktok%e5%88%b7%e7%b2%89%e7%ae%97%e6%b3%95%ef%bc%9a%e7%b2%89%e4%b8%9d%e5%92%8c%e7%82%b9%e8%b5%9e%e8%b6%8a%e5%a4%9a%e6%8e%92%e5%90%8d%e8%b6%8a%e9%ab%98%e5%90%97/
https://trendburst.us/tiktok%e5%88%b7%e7%b2%89%e3%80%81tiktok%e4%b9%b0%e7%b2%89%e3%80%81tiktok%e5%88%b7%e8%b5%9e%e3%80%81tiktok%e4%b9%b0%e8%b5%9e%e3%80%81tiktok%e5%88%b7%e6%92%ad%e6%94%be%e9%87%8f%e3%80%81tk%e5%88%b7/
https://padlet.com/lwf876/fbfensi
https://sites.google.com/view/fbfensi
https://sites.google.com/view/ytshuafensi
https://sites.google.com/view/instagramshuafensi
https://sites.google.com/view/facebookshuafensi
https://sites.google.com/view/twittershuafensi
https://sites.google.com/view/tiktokshuafensi
https://sites.google.com/view/telegramshuafensi
https://sites.google.com/view/linkedinshuafensi
https://iglike.online/
https://instagram.iglike.online/
https://tiktok.iglike.online/
https://youtube.iglike.online/
https://facebook.iglike.online/
https://twitter.iglike.online/
https://telegram.iglike.online/
https://linkedin.iglike.online/
https://ifans.vip/
https://instagram.ifans.vip
https://tiktok.ifans.vip
https://youtube.ifans.vip
https://facebook.ifans.vip
https://twitter.ifans.vip
https://telegram.ifans.vip
https://linkedin.ifans.vip
https://daishuafensi.com/
https://instagram.daishuafensi.com/
https://tiktok.daishuafensi.com/
https://youtube.daishuafensi.com/
https://facebook.daishuafensi.com/
https://twitter.daishuafensi.com/
https://telegram.daishuafensi.com/
https://linkedin.daishuafensi.com/
https://fbfensi.com/about
https://fbfensi.com/blog/insfensi
https://fbfensi.com/blog/Instagram-shuafensi
https://fbfensi.com/blog/FB-shua-fensi
https://fbfensi.com/blog/tiktok-shua-fensi
https://fbfensi.com/blog/Twitter-shua-fensi
https://fbfensi.com/blog/youtube-shua-fensi
https://fbfensi.com/blog/Telegram-shua-fensi
https://fbfensi.com/services
https://blog.fbfensi.com/
https://blog.fbfensi.com/tkshuafen-tkshuazan/
https://blog.fbfensi.com/tkshuafensi/
https://blog.fbfensi.com/tiktokshuafensi-tiktokshuadianzan/
https://blog.fbfensi.com/tiktokfensi-zengjiapaiming/
https://blog.fbfensi.com/tiktok-zengjia-fensi/
https://blog.fbfensi.com/instagrammaifensi/
https://blog.fbfensi.com/tiktok-shua-fensi/
https://blog.fbfensi.com/youtube-shua-fensi/
https://blog.fbfensi.com/ins-shua-fensi/
https://blog.fbfensi.com/facebook-shua-fensi/
https://www.tiktok.com/@fbfensi
https://www.tiktok.com/@fbfensi/video/7255596440632823041
https://www.tiktok.com/@fbfensi/video/7255595335706299650
https://www.tiktok.com/@fbfensi/video/7255594077087927554
https://www.tiktok.com/@fbfensi/video/7255592879282752769
https://www.tiktok.com/@fbfensi/video/7255591658106948865
https://www.tiktok.com/@fbfensi/video/7255589892082683138
https://www.tiktok.com/@fbfensi/video/7255572756350176514
https://vipfensi8.medium.com/
https://twittershuafenpingtai.medium.com/
https://facebookfensi.medium.com/
https://shuafensi.medium.com/
https://medium.com/@wiktoriyaelchaninova70
https://insshuafensi.medium.com/
https://youtubeshuafensi.medium.com/
https://fensi163.medium.com/
https://instagramfensi.medium.com/
https://daishuafensi.medium.com/
https://inshuarenfen.medium.com/
https://instagramhuarenfensi.medium.com/
https://tiktokshuafensi.medium.com/
https://twittershuafensi.medium.com/
https://maifensi.medium.com/
https://fbdianzan.medium.com/
https://fbfensi.medium.com/
https://youtubefensi.medium.com/
https://insxox.medium.com/
https://velmago01900493.medium.com/
https://sararos01067668.medium.com/
https://tinacar27854818.medium.com/
https://instagramhuarenfensi.medium.com/
https://tabitapin.medium.com/
https://jenolso72951261.medium.com/
https://vipshuafensi.medium.com/
https://igshuafensi.medium.com/
https://x.com/fbmaifensi
https://www.sotwe.com/fbmaifensi
https://www.webnovel.com/zh/book/instagram%E5%88%B7%E7%B2%89%E5%B9%B3%E5%8F%B0-%7Cinstagram%E4%B9%B0%E7%B2%89%E5%B9%B3%E5%8F%B0_33538896008457105
https://twitter.com/Michell13465888/status/1501587673924120576
https://twitter.com/Michell52040350/status/1501585266783313929
https://www.facebook.com/vipfensi8/
https://fbfensi.hashnode.dev/fbmaifensi
https://fbfensi.hashnode.dev/instagramshuafensi
https://fbfensi.hashnode.dev/youtubemaifensi
https://open.spotify.com/playlist/3QaTAdgFze4dlBhxCPAYCq
https://cn.anotepad.com/notes/hy22yae4
https://cn.anotepad.com/notes/rffdk9ci
https://cn.anotepad.com/note/read/4k49q9ae
https://anotepad.com/@shuafensi
https://anotepad.com/@fbfensi
https://gravatar.com/fbfensi
https://steemit.com/@fbfensi/
https://steemitwallet.com/@fbfensi/permissions
https://vimeo.com/insfensi
https://instagramshuafenpingtaishuafensivip.quora.com/
https://www.quora.com/profile/Instagram%E5%88%B7%E7%B2%89
https://www.wattpad.com/user/insshuafen
https://www.wattpad.com/story/400143157-
https://www.webnovel.com/zh/profile/4503920760
https://bsky.app/profile/skcie38999.bsky.social
https://bsky.app/profile/skcie38999.bsky.social/post/3lwogdvuz5c2i
https://bsky.app/profile/skcie38999.bsky.social/post/3lwogbf2jks2i
https://bsky.app/profile/skcie38999.bsky.social/post/3lwog54v24c2i
https://bsky.app/profile/skcie38999.bsky.social/post/3lwofz4vqck2i
https://bsky.app/profile/skcie38999.bsky.social/post/3lwofvmoif22i
https://bsky.app/profile/skcie38999.bsky.social/post/3lwofrsf7rk2i
https://bsky.app/profile/skcie38999.bsky.social/post/3lwofpxelas2i
Instagram刷粉 Instagram买粉 Instagram刷粉平台 Ins买粉 ins刷粉 ins刷粉平台 Instagram播放量 ins刷赞 FB买粉 INS买粉 YT买粉 X买粉 TG买粉 Li买粉 TK买粉 Facebook刷粉 Instagram刷粉 YouTube刷粉 TikTok刷粉 Twitter刷粉 Telegram刷粉 LinkedIn刷粉 Facebook刷粉 Instagram刷粉 YouTube刷粉 TikTok刷粉 Twitter刷粉 Telegram刷粉 LinkedIn刷粉 FB刷粉 INS刷粉 YT刷粉 TK刷粉 X刷粉 TG刷粉 Li刷粉 FB刷粉平台 通过TikTok刷粉、TikTok刷赞、TikTok刷播放量快速提高账号权重,让账号视频排名靠前 Instagram刷粉 Instagram买粉 ins买粉 ins刷粉 ins刷赞 ins刷赞 ins买赞 YouTube刷粉 YouTube买粉 YT刷赞 YT买赞 YT刷播放量 YT刷订阅 油管刷粉 Facebook刷粉 Facebook买粉 FB刷赞 FB买赞 FB刷播放量 FB刷表情赞 YT刷粉、TK刷粉、X刷粉、TG刷粉、Li刷粉、FB刷粉、INS刷粉 Telegram刷粉 FB刷粉 INS刷粉 YT刷粉 TK刷粉 X刷粉 TG刷粉 Li刷粉 FB买粉 INS买粉 YT买粉 TK买粉 X买粉 TG买粉 FB刷粉 INS刷粉 YT刷粉 TK刷粉 X刷粉 TG刷粉 Li刷粉 FB买粉 INS买粉 YT买粉 TK买粉 X买粉 TG买粉 Li买粉
INS买粉丝、INS刷粉、INS买赞、INS刷赞 INS买粉丝 INS刷粉 INS买赞 INS刷赞 TG买粉 X买粉 TK买粉 YT买粉 INS买粉 FB买粉 Li买粉 Ins买粉 INS刷粉 INS买赞 INS刷赞 INS买粉 INS刷粉 INS买赞 INS刷赞 INS刷播放量 Instagram买粉平台 Ins买粉平台 Ins买粉 INS刷粉 INS买赞 INS刷赞 INS买粉平台 Instagram刷粉 Instagram买粉 Instagram刷赞 Instagram买赞 Instagram刷播放量 Instagram刷收藏 Instagram刷粉平台 Instagram华人粉 Facebook刷粉 Instagram刷粉 YouTube刷粉 TikTok刷粉 X刷粉 Telegram刷粉 FB刷粉平台 FB买粉平台 Facebook买粉 Instagram买粉 YouTube买粉 TikTok买粉 X买粉 Telegram买粉 油管刷订阅 推特刷粉 脸书刷粉 电报刷粉 TikTok刷粉 TikTok买粉 TikTok刷粉 购买抖音Tiktok刷粉丝 Tiktok刷播放量观看量浏览量 Tiktok刷点赞 Tiktok刷粉平台 Tiktok刷赞平台 抖音刷粉丝 抖音刷点赞 抖音刷粉丝平台 抖音刷点赞平台 购买Tiktok粉丝 Tiktok买粉丝 Tiktok视频快速增加观看次数 Facebook刷粉 购买脸书Facebook粉丝 Facebook刷播放量 Facebook刷点赞 Facebook刷粉丝平台 Facebook买粉丝平台 脸书买粉丝 脸书刷粉丝 脸书转发分享 脸书怎么买粉丝 脸书爆粉 脸书买粉丝买点赞 购买Facebook粉丝的平台 Facebook专页怎么加关注和点赞 Facebook怎么快速排名 Twitter刷粉 购买推特粉丝 Twitter刷播放量 Twitter刷浏览量 Twitter刷点赞 Twitter刷粉平台 Twitter刷赞平台 推特刷粉丝 推特刷粉丝平台 推特刷转发 YouTube刷粉 购买油管YouTube粉丝 YouTube刷订阅 YouTube刷播放量 油管刷粉丝 油管刷点赞 YouTube刷时长 YouTube刷播放量 YouTube买点赞 YouTube刷观看量 购买Instagram粉丝 Instagram刷粉丝 Instagram刷播放量 Instagram华人粉 Instagram华人赞 Instagram刷点赞 Instagram刷粉平台 Instagram刷赞平台 Instagram刷粉丝 YouTube刷粉丝 Facebook刷粉丝 Twitter刷粉丝 Tiktok刷粉丝 刷粉丝平台 刷点赞平台 FB刷粉…