Heat Pump Pressure Switches

Updated: Mar 2


Pressure switches are typically installed in heat pumps and air conditioning systems to protect the compressor from a high pressure situation, to protect the compressor in a low refrigerant situation, and to control the condenser fan cycling.



High and low pressure switches may be installed on the refrigerant tubing of some air conditioning systems. However, they are commonly found on heat pumps. In the case of a heat pump in cooling mode, the high pressure switch is used to make sure that outdoor unit can reject heat with the outside air. In heating mode this same high pressure switch makes sure that the indoor unit is able to reject enough heat inside the building so that the discharge pressure does not exceed the internal relief pressure. This could happen if the duct collapsed, the filter was clogged, dust covered the return side of the indoor coil, the blower speed was too low or the blower motor was broken.


The fan cycling pressure switch which is found on the discharge gas line will also help if the indoor coil is having a hard time rejecting heat because it controls what pressure the outdoor fan will turn on at and what pressure it will turn off at. If the outdoor coil is absorbing more heat than the indoor coil can reject then the discharge pressure will start to rise.


In one example of an R410A heat pump with a fan cycling switch installed, when the discharge pressure rises to 425psi, the fan will shut off and when the pressure goes down to 350 psi, the fan will turn back on. Also, after the compressor initially turns on, the pressure must rise to 350psi to even turn on the fan.

The low pressure safety switch is normally closed when the system is off if the system has saturated refrigerant inside. When the unit turns on, one side of the system rises in pressure and one side lowers in pressure. If the pressure is too low on the low side of the system, this switch will open the 24v electrical circuit going to either the contactor or the defrost board safety switch terminal. This switch may open if the unit is low on refrigerant or if there is a major clog in the liquid line part of the system such as the filter drier, metering device, distributor tubes, or strainer.


To learn more about pressure switches and testing view this video- https://youtu.be/8VtbJldahOI



Check out our book “Refrigerant Charging and Service Procedures for Air Conditioning”.

The full outline is available at https://www.acservicetech.com/the-book

If you have already purchased our book, be sure to tell local HVACR Instructors about our book and what you think of it. We would love to get the book into the hands of the next generation of HVACR Technicians!

Published: 4/5/2019

Author: Craig Migliaccio

About the Author:Craig is the owner of AC Service Tech LLC and the Author of the book “Refrigerant Charging and Service Procedures for Air Conditioning”. Craig is a licensed Teacher of HVACR, Sheet Metal, and Building Maintenance in the State of New Jersey of the USA. He is also an HVACR Contracting Business owner of 15 years and holds an NJ HVACR Master License. Craig creates educational HVACR articles and videos which are posted at https://www.acservicetech.com & https://www.youtube.com/acservicetechchannel

8 Comments


rotie brown
rotie brown
4 days ago

It’s fascinating how high and low pressure switches help keep heat pumps operating safely and efficiently—so many factors can affect performance! While learning about HVAC systems, I sometimes play Crossy Road, an arcade game where you guide characters across roads and rivers. Timing and attention to detail matter just as much in both

Like

A B
A B
Mar 29

land for sale belize are nice lands for investments and opportunities for an inspiring work!


Like

Great breakdown of how heat pump pressure switches actually work and why they’re so critical for system safety. I especially liked the explanation of high vs. low pressure switches—it really highlights how they protect the system from damage and inefficiency. Definitely Geometry Dash useful for both beginners and technicians trying to understand HVAC diagnostics better.

Like

Als es neulich in Rheinland-Pfalz wie aus Kübeln regnete, brauchte ich in meiner Ferienwohnung dringend eine Beschäftigung. In einem Spiele-Forum wurde mir für eine Runde Poker play jonny empfohlen, was genau meinen Geschmack traf. Die Plattform hat eine angenehme Atmosphäre und man findet sich dort sofort gut zurecht. Einige spannende Stunden habe ich dort verbracht und konnte meine Strategie erfolgreich einsetzen. Wenn das Wetter draußen alles durcheinanderbringt, ist das eine wirklich gute Alternative.

Like

The fan cycling switch managing discharge pressure between 350–425 psi helps maintain stable operation, while the low-pressure safety switch prevents damage if refrigerant levels drop or a restriction occurs. Understanding these controls makes troubleshooting far more precise — the kind of technical awareness and performance focus you’d expect from a SoFlo Wheelie Life mindset.

Like
AccuTrak ad
danfoss ad
Asurity-Digital-Ads_High_Res_1080x360.jp
AC Service Tech Ad
Join Our Updates List!

AC Service Tech HVAC Training is made possible by continued support from our visitors, customers, and support from these Sponsors!

NAVAC LOGO Black_edited.png
Accutrak Logo
TruTech-Tools-Logo-Main (3)[528].png
HavenRGB-FC w_grey horz.png

AC SERVICE TECH, LLC

Updates List

Thanks for submitting!

Thanks for all your continued support! I appreciate all the comments, questions, and responses that I receive from each of you. I look forward to responding to many more! If you have an HVACR related question, drop it in the comment section of one of the YouTube videos at the AC Service Tech YouTube Channel and I will do my best to respond.

 

For business related inquires email us at info@acservicetech.com

Check back regularly as we are always updating and improving this website!

© 2026 AC Service Tech, LLC.

bottom of page