top of page
Slide for homepage w stroke.jpg

10 Methods to Clean Condensate Drains/Traps on Air Conditioners

Updated: Feb 24

In this article, we go over 10 methods to clean out condensate drain lines and traps on air conditioning systems! The condensate drain line is responsible for removing the water that is extracted from the indoor air (humidity) during air conditioning mode. Over time, the drain trap and/or line can become clogged with dirt, dust, bio-growth, and other debris. When this happens, the water may back up into the system, overflowing out of the primary drain pan and causing damage to the system and/or building.


Let's discuss the fastest methods for clearing these lines/traps. To prepare for cleaning, the system's power must first be switched off so that air is not being pushed or pulled through the drain line/trap. Also, if you have access to the trap, remember to fill it back up with water when you are done and cap off any service access openings when complete.


ree

Method #1: Using a Shop Vac to Evacuate The Drain Line at the Outside Location


Simply connect the wet/dry vacuum hose to the end of the drain line outside and turn on the vacuum. The suction will help remove any blockages or debris in the line. To better clean out the lines, add water at the indoor unit primary pan or the line's service access location while doing this!

ree

Method #2: Blowing out the Condensate Line with 30 PSI of Compressed Air using an Extended Tip.

To get a better seal inside the tubing, wrap the end of the extended tip with electrical tape. Then, place the tip down into the trap and apply the compressed air to blow out the debris. Make sure to not apply excessive pressure because this could cause a pipe joint to separate and leak. When finished, fill the trap back up with water and replace the cap.

ree

ree

Method #3: Clear the Trap Using a Brush

Remove the caps on both ends of the condensate trap. Pull the brush through the trap to break up clogs and extract debris. When finished, fill the trap back up with water and replace the caps.

ree

Method #4: Clearing The Drain Line at a Horizontal Tee With A Shop Vacuum

When there is a horizontal access tee, use a 1/2" CPVC 90° fitting with a section of CPVC pipe attached to a 3/4" PVC bushing, to access the inner pipe. The 3/4" bushing typically fits into the shop vac's hose end. This assembly can be used to blow or suck out debris inside the horizontal section of pipe. Remember to fill the trap with water and replace any service caps when complete.

ree

ree

Method #5: Vacuum the Trap Using a Shop Vac Hose with a Section of CPVC Pipe Attached to the End.

Simply connect the 3/4" to 1/2" pipe to the end of the shop vac and insert it into the condensate trap. Remember, attaching electrical tape to increase the diameter of the 1/2" CPVC pipe will allow it to seal better when inserted into the trap. Turn on the shop vac. Remember to fill the trap with water and replace the service caps when complete.

ree

ree

Method #6: Blow Out the Condensate Trap Using the Shop Vacuum

A shop vac can be used to blow out the trap instead of sucking out the debris. In this scenario, move the vacuum hose end to the outlet of the shop vac instead of at the inlet. Then insert the 1/2" CPVC pipe into the trap and turn on the vacuum. Remember to fill the trap with water and replace the service caps when complete.

ree
ree

Method #7: Blowing Out a Condensate Trap With Clear Vinyl Tubing Only In the absence of an accessible electrical outlet or pressurization device, you can use a clear vinyl tube with electrical tape on the end inserted into the trap. At the exposed open end of the clear vinyl tube, apply force through the tubing with a large breath.

ree

ree

Method #8: Applying 30 PSI of Nitrogen Through a Cone End to Blow Out The Condensate Trap.

A nitrogen tank can act as an alternative to compressed air. Attach a hose and air gun to the nitrogen regulator and set the secondary regulator to 30 PSI. Apply the air gun end to the open section of pipe and allow the nitrogen to blow out the clog. When finished, fill the trap back up with water and replace the cap.

ree

ree

Method #9: Applying 30 PSI of Nitrogen Through an Extension Tube to Blow Out the Condensate Trap.

Attach a hose and air gun to the nitrogen regulator and set the secondary regulator to 30 PSI. Add the extension tube with electrical tape on the end to the air gun. Put the extension tube down into the trap and allow the nitrogen to blow out the clog. When finished, fill the trap back up with water and replace the cap.

ree

ree

Method #10: Using Pressurized Air Through a Flexible Extension Hose

To get to hard to reach places, a small flexible extension hose can be added to the air gun. Fish the flexible hose end (poly tube end) into the open section of the condensate drain line. Cover the remainder of the opening and then apply the air/nitrogen pressure through the drain line. This method can be used when there is no service access cap or when the only access is the primary drain pan outlet.

ree

A Quick Note: Method #1 is a preferred method because not only is the clog removed, but the entire drain line can be flushed by adding water into the indoor service access cap or drain pan. Always add water back into the trap when complete! This stops any air from being pulled or pushed through the drain line and allows water accumulating in the primary pan to drain out properly.

Want to see these methods in action? Check out our YouTube Short! https://youtube.com/shorts/MkHgXlt9p8M Learn more about the function of the condensate trap by watching our videos below! Check out our free Quizzes to test your knowledge here! Check out our Free Calculators here! If you want to learn about refrigerants and how they work in a system, check out our “Refrigerant Charging and Service Procedures for Air Conditioning” book . Test your knowledge with our 1,000 question workbook along with the answer key! We also have quick reference cards for use out in the field! Bundle Packs are a great way to save and get faster shipping! Check out www.acservicetech.com/store Tools that we use: www.amazon.com/shop/acservicetechFollow us on Facebook for Quick Tips and Updates here!



ree

Published: 5/10/23 Author: Craig Migliaccio


About the Author: Craig is the owner of AC Service Tech LLC and the Author of the book “Refrigerant Charging and Service Procedures for Air Conditioning”. Craig is a licensed Teacher of HVACR, Sheet Metal, and Building Maintenance in the State of New Jersey of the USA. He is also an HVACR Contracting Business owner of 17 years and holds an NJ HVACR Master License. Craig creates educational HVACR articles and videos which are posted at https://www.acservicetech.com & https://www.youtube.com/acservicetechchannel

 
 
 

6 Comments


Javon
Javon
Dec 16

Contacts on https://project-source.pissedconsumer.com/review.html I had the opportunity to utilize Project Source Pools, Spas, and Plumbing Supplies, and I must say, the experience was commendable. The quality of the products offered is exceptional, with a wide range of options that cater to various needs. The staff was knowledgeable and provided valuable assistance, ensuring I found exactly what I required. Additionally, the ease of navigation within the store made the shopping experience efficient and enjoyable. Overall, I highly recommend Project Source for anyone seeking reliable supplies for their pool, spa, or plumbing projects.

Like

Nice breakdown of drain-trap cleanup methods — you make it sound actually doable. One extra tip: in humid areas consider scheduling a pro flush like the folks at https://cleaning-sarasota.com/ , just to catch hidden buildup. Keeping that line clear = fewer surprise leaks.

Edited
Like

This article provides great insights into maintaining air conditioners by properly cleaning condensate drain traps. It’s essential to keep these components clear to ensure the system runs efficiently. For anyone handling such maintenance tasks, it’s important to use high-quality cleaning agents and chemicals. Working with a reliable chemical company like Brody Chemical can ensure you're using the right products that won't harm your equipment. Their specialized cleaning solutions are designed for various needs, from HVAC systems to industrial applications, making maintenance tasks easier and more effective. With the right chemicals, these maintenance methods can really make a difference!

Like

Bruce T Mathieu
Bruce T Mathieu
Aug 05, 2024

Great information about how to clean a condensate drain and line

Like

wrighttchristian
Apr 26, 2024

This is a wonderful information that can help new beginners who joined AC Repair business. Thank you so much for sharing.

Like
AccuTrak ad
danfoss ad
Asurity-Digital-Ads_High_Res_1080x360.jp
AC Service Tech Ad
Join Our Updates List!

AC Service Tech HVAC Training is made possible by continued support from our visitors, customers, and support from these Sponsors!

NAVAC LOGO Black_edited.png
Accutrak Logo
TruTech-Tools-Logo-Main (3)[528].png
HavenRGB-FC w_grey horz.png

AC SERVICE TECH, LLC

Updates List

Thanks for submitting!

Thanks for all your continued support! I appreciate all the comments, questions, and responses that I receive from each of you. I look forward to responding to many more! If you have an HVACR related question, drop it in the comment section of one of the YouTube videos at the AC Service Tech YouTube Channel and I will do my best to respond.

 

For business related inquires email us at info@acservicetech.com

Check back regularly as we are always updating and improving this website!

© 2025 AC Service Tech, LLC.

bottom of page