Ductless Mini-Split Installation Step by Step
In this step by step installation, we will be covering the full installation of a Ductless Mini-Split heat pump system. This system happens to be a Cooper&Hunter Dakota Series Hyper Heat model. This installation process will be very similar to other manufacturer’s Mini-Split systems. However, make sure to read the install instructions and flare torque specs of the exact model that you are installing. The installation of a Mini-Split Ductless system takes a variety of tools and techniques to accomplish and we will be covering each of them as we move through the steps. Step 1. Locate the general area in which the indoor and outdoor units need to be mounted. When possible, plan to install the indoor head unit on the inside of an exterior wall. Do this in a location where the line set tubing can exit through the wall and go directly down to the outdoor unit connection points. The indoor unit location should be away from fluorescent lights as this may interfere with the system’s remote-control operation. Make sure that the location of the indoor unit allows for easy access to the air filter located at the top of the indoor wall unit. Next, determine if the outdoor unit needs to be hung on a concrete wall with a bracket, mounted to an elevated deck, or is sitting on a pad near the ground level. System installed in this article: https://amzn.to/3aXbmyV Mini-Split Wall Bracket: https://amzn.to/2YG1THv Step 2. After the general install area is known for the indoor and outdoor units, start with the indoor unit. Locate the wall studs with a stud finder or by knocking. Confirm the stud locations. Mount the indoor unit wall plate to the studs with weight bearing fasteners with a large head. Lags with washers or screws with washers will work. Step 3. Determine the location of the hole that must be cut through the exterior wall. This is done for the line set tubes, electrical wire, and condensate line to travel through to the outside. This will be a single hole usually 2 3/8” or smaller in diameter. To determine where the hole needs to be located, use the carboard template from the manufacturer or with measurements from the back side of the indoor unit. Draw the circle lightly with a pencil. Drill a screw into the sheetrock at the center of the circle to see if there is a stud in the way. Next, drill two more screws on the outer horizontal edges of the circle to make sure that there is not a stud in either spot. If there is a stud located where the hole needs to be, the metal wall plate for the indoor head unit will need to be shifted horizontally so that the 2 3/8” hole will miss the stud. Step 4. To probe through the wall, draw a small X on the wall where the center of the hole will be. Place a metal probe (actually an insulation hanger) into the drill chuck just like a drill bit. Drill through the X with the probe on a slight downward angle through the sheetrock, insulation, plywood and siding. Find where the probe exits through the outside wall. Determine if this location is satisfactory for the line set to exit through. Step 5. To drill the hole through the interior wall, determine the size hole-saw bit to place into the drill. If you would like to sleeve the hole with 2” schedule 40 PVC, use a 2 3/8” hole-saw bit. Drill through the sheetrock slowly on a slight downward angle. Step 6. Before drilling the hole through the exterior siding and sheathing, switch the drill to counterclockwise (reverse). Use the drill bit in reverse to lower the risk of cracking the siding while drilling a hole through it. Get the pilot bit of the hole-saw to penetrate the siding fist. Then, keep the drill at steady angle and apply the least amount of force possible as you drill the 2 3/8” hole through the siding. Less pressure avoids the outer bit from catching on the siding and tearing a crack into it. Keeping the drill at a high RPM may help as well. Make sure that this hole is going on an angle slightly upward. Complete the hole by penetrating through the plywood sheathing. Push the interior wall insulation to the sides so that nothing is blocking the hole through to the inside. Step 7. If using a sleeve, push the sleeve material through, mark the ends with pencil, and pull the sleeve out. Cut the sleeve to size using a hand saw. In this instance, a 2” PVC sleeve is used. Slide the finished sleeve into position and put a screw through the sleeve and into the plywood sheathing so that the sleeve will not move when pushing the line set tubes through it. Also, add sealant where the PVC meets the siding and where the sleeve meets the sheetrock. Step 8. Plan for the connection of the electrical wiring to the back of the indoor head unit. The normal wiring supplied with Mini-Splits has an outside rubber casing that is UV protected and outdoor rated. Inside the casing there are four separate stranded wires. Three are for the communication/power and one is for the ground. Remember that the communication wires have high voltage power running through them so make sure to follow local codes when installing the wiring from the indoor unit to the outdoor unit. Some jurisdictions do not allow the high voltage cable to be exposed and unshielded outside the building. In this case, a watertight shielding such as flexible conduit must be installed to protect the cable. Step 9. If the cable https://amzn.to/3biNhmx must be protected, run the cable inside flexible outdoor conduit or use Southwire EZ-IN https://amzn.to/2zrYX52. Determine the length of conduit https://amzn.to/3lDMilA needed and add a few extra feet to be safe for distance. Fish the cable through the conduit and leave roughly 18” of extra cable past the conduit on both sides. If EZ-IN is used, the four wires are already inside the conduit. Step 10. Add a connector to the end of the conduit to connect the conduit to the back of the indoor head unit. First, slide the four wires through the hole in the indoor head unit and the affix the conduit connector in place. The wires will now be extending out of the front electrical compartment. Step 11. Mount each of the three communication wires to the terminals in the front of the indoor head unit and tighten each in place. Note what color wire is mounted on each terminal designated as A, B, C or 1, 2, 3. These same color wires will be mounted to the matching A, B, C or 1, 2, 3 terminals at the outdoor unit. The green wire must be connected to the ground frame of the indoor unit and the outdoor unit. Step 12. Carefully bend the copper line set tubes on the back of the Mini-Split 90 degrees so that they face toward the wall and are lined up to go through the hole in the wall. Also, bend the tubing on a slight downward angle. Step 13. Tape the condensate line and electrical cable/conduit together with the line set tubes. When doing this, make sure that the condensate line is positioned at the bottom so that the water will travel properly when installed. To secure these together, electrical tape is good to use because with each wrap, you can squish these lines together to reduce the outside dimension of the objects within the tape. This helps make it easier to fish the objects through the hole in the wall. Step 14. Fish the objects through the hole/sleeve in the wall and hook the indoor wall unit onto the metal mounting plate. Make sure that the indoor wall unit is hooked at the top and snaps into position at the bottom. Step 15. Mount the remote to the inside wall if desired. Now the indoor work is complete. Step 16. Move outside and cut off the tape carefully from the electrical wiring, condensate line, and the line set tubes. Step 17. Bend the line set tubes by hand one at a time. In order to do this, place a hold back finger or two inside the hole in the wall to support the bottom of the tube. With the other hand pull down on the tube. Move the hold back fingers in different spots as you are bending the tube downward. This will make sure that the tube does not kink because there is not only one bend spot but many. Step 18. Prepare the copper tube line set which will connect from the stubs of the indoor head unit to the outdoor unit. To prepare the tubing, uncoil each tube by holding the end of the tube down with your foot and rolling out the coil on a concrete walkway or the ground. This will produce a straight section of tube. Determine the length needed by measuring the distance from the stubs of the indoor unit to the outdoor unit connectors. After determining the distance, add a few feet and cut each tube to length using a utility knife to cut the outer insulation and a tubing cutter for the tube. Step 19. Hold the end of the tube in the downward position and deburr the end of the tube with a deburring tool. Add the flare nut at the end of the tube and slide the nut further up the tube. Put the copper tube into a flaring tool block and lock it in place. Step 20. To produce a high-quality flare, use an Eccentric Flaring tool https://amzn.to/2OBxGlMl or https://amzn.to/367jBXj. Make sure that the tube is roughly 1/8” out of the flare block. If the flaring tool has a tubing stop built into it, push the tube into the mechanism until the tube cannot move inward anymore. Lock the tube in place (REMEMBER TO HAVE THE FLARE NUT ON THE TUBING). Make sure that there is a dab of refrigerant oil or Nylog https://amzn.to/2MLJcch on the eccentric cone. Rotate the cone clockwise toward the copper tube until the eccentric tool clutch opens up. This means that the flare is complete. Back the cone up counterclockwise out of the way and then release the copper tube from the block. Push the nut forward over the flare. Do this for both line set tubes. Step 21. Add a small amount of Nylog or a dab the matching refrigerant oil that the system has to the flare face. When using Nylog, only a very small amount must be used and only on the flare face and flare adapter so it does not enter the inside of the tube. Push the flare face and flare adapter together and rotate the nut until it stops moving. Step 22. Locate the ft/lb torque specifications for the tubing size in the manufacturer’s manual. In this case, the ft/lb torque of this model unit was 11.8 ft/lbs for ¼” tubing and 19 ft/lbs for 3/8” tubing. Hold the flare adapter in place with an adjustable wrench and place a torque wrench https://amzn.to/2NRR68Q on the flare nut. Tighten to the specified torque value. Do this for both line set tubes at the specified torque value for each. Step 23. Bend the remaining line set tubing into place and cut the ends to length so that they meet the connectors on the outdoor unit. Step 24. Debur the ends of the tubes with each tube in the downward position so that any copper shards fall out of the tube instead of into the tube. Step 25. To produce a high-quality flare, use an Eccentric Flaring tool. Make sure that the tube is roughly 1/8” out of the flare block. If the flaring tool has a tubing stop built into it, push the tube into the mechanism until the tube cannot move inward anymore. Lock the tube in place (REMEMBER TO HAVE THE FLARE NUT ON THE TUBING). Make sure that there is a dab of refrigerant oil or Nylog on the eccentric cone. Rotate the cone clockwise toward the copper tube until the eccentric tool clutch opens up. This means that the flare is complete. Back the cone up counterclockwise out of the way and then release the copper tube from the block. Push the nut forward over the flare. Step 26. Add a small amount of Nylog https://amzn.to/2MLJcch or a dab the matching refrigerant oil that the system has to the flare face. When using Nylog, only a very small amount must be used and only on the flare face and flare adapter so it does not enter the inside of the tube. Step 27. Push the flare face and flare adapter together and rotate the nut until it stops moving. Use the same ft/lb torque specifications for each tube size just like before as found in the manufacturer’s manual. Hold the flare adapter in place with an adjustable wrench and place a torque wrench on the flare nut. Tighten to the specified torque value. Do this for both line set tubes at the specified torque value for each. Step 28. Pressure test the system to see if there are any leaks at the flare joints or in any other location. This can be done at a nitrogen pressure of 300 psi on newer systems for at least ten minutes, preferably an hour. On older systems, test at a lower pressure so that you do not make a leak by adding excessive pressure. Using a digital manifold set will allow the technician to see incremental changes during the pressure test and it will allow the tech to know if there is a leak faster if there is a drop in pressure. Always make sure to follow manufacturers’ specifications for the exact amount of nitrogen pressure to test the system to as those specifications will supersede these instructions. Step 29. To pressure test, use a 60 cu ft nitrogen tank with a regulator http://amzn.to/2bXdR5f and a manifold gauge set http://amzn.to/2aenwTq along with hoses http://amzn.to/2aBumVI. The first gauge on the nitrogen regulator shows the pressure in the tank and the second gauge shows the pressure exiting the regulator. Before opening the tank, make sure that the thumb screw to the regulator is turned counterclockwise outward. The ¼” port on the regulator connects to a manifold gauge set via the yellow service hose attached to the middle of the manifold gauge set. Connect the blue hose from the gauge set to the port on the vapor line of the outdoor unit. To do this, use a 5/16” to ¼” adapter https://amzn.to/34HSran to reduce the port size of the outdoor unit to the hose size. Keep the manifold gauge set handles shut for now and open the nitrogen tank handle. Next turn the thumb screw on the nitrogen regulator clockwise to the desired pressure. Next, bleed the air out of the hoses at the gauge set and then reconnect to the system. Open the blue handle on the gauge set to allow the nitrogen into the system. Shut the handle upon reaching the desired pressure. After the handle is shut, tap on the gauge and note the pressure measurement. Also make sure to shut the handle on top of the nitrogen tank and detach the yellow hose from the regulator. Release the nitrogen from the regulator and back out the thumb screw on the regulator counterclockwise for safety. Step 30. Perform a ten minute (preferably an hour) or longer pressure test to see if the pressure falls. During this test while there is high pressure in the system, add “Big Blu” bubble leak detector onto the joints. This is an anti-corrosive liquid leak detector solution that will make a bubble or foaming action at a leak location. Do not use dish detergent and water as the chemicals in dish detergent can eat away at fittings over time. Step 31. If there are no leaks found because there is no pressure drop, wipe off the excess leak detector from the joints and release the nitrogen pressure slowly from the manifold. After the tubing pressure is at 0 PSIG, detach the manifold gauge set to vacuum the tubing system. Step 32. Prior to setting up for vacuum, remove the valve core (Schrader valve) from the 5/16” port of the system with a valve core removal tool if you have not done so already. Also remove the valve core from the top side of the 5/16” valve core removal tool. Leave the body of this valve core removal tool in place on the 5/16” port and add another ¼” valve core removal tool to the top part of the first tool. This is to add a vacuum gauge at this location. Step 33. To connect the vacuum hose setup to the system, run one vacuum hose from the vacuum pump to the end of the 5/16” valve core removal tool. The valve on the 5/16” valve core removal tool is used to trap the vacuum and the valve above it on the ¼” tool is to isolate the vacuum gauge. At this point, keep both valves in the open position. Tools used for the Vacuum: Appion Red 3/8" to 1/4" Vacuum Hose - http://amzn.to/2uYg6Ro CPS Vacuum Micron Gauge - http://amzn.to/2v1nM3O CPS 4 CFM Vacuum Pump - https://amzn.to/2DxgPwY 1/4" Appion Valve Core Removal Tool - http://amzn.to/2uYr8WL 5/16" Appion Valve Core Removal Tool - https://amzn.to/2JHmfbP Step 34. After the vacuum setup is attached, turn on the vacuum pump. Allow the vacuum gauge to reach roughly 1,000 microns before closing and then reopening both valves on the valve core removal tools. This is done to remove any air surrounding the valves. Step 35. Allow the gauge to reach roughly 200 microns, close the valves again, and then reopen them. The micron level may rise to roughly 250 microns after moving the valves. Allow the gauge to reach 200 microns again and this time, shut the one valve on the 5/16” valve core removal tool. Shut the vacuum pump off. (Per EPA 608 guidelines, a vacuum of 500 microns must be attained prior to allowing refrigerant into the tubing.) Step 36. Wait at least ten minutes with the vacuum pump isolated from the system to see if the micron level rises. Remember that the vacuum gauge is connected to the system and reading the true vacuum level while the pump is off. This test is referred to as the “Ten Minute Standing Vacuum Test” or the “Decay Test”. If the vacuum level rises continually, there is a leak. If the vacuum level rises and then plateau’s, there may be water in the system. Step 37. If the vacuum level stays below 500 microns and does not continue to rise, the vacuum is good. Either break the vacuum with refrigerant from the bottle or by opening the service valves on the system. If the line set length does not exceed the maximum length posted by the manufacturer, the service valves can just be opened because the refrigerant charge amount does not need to be increased. Prior to opening the service valves, close the valve core removal tool valve to isolate the vacuum gauge. This will protect the vacuum gauge sensor from refrigerant oil and positive pressure. Step 38. Open the service valves on the system with the appropriately sized Allen wrench or ratcheting wrench. Replace the valve core at the 5/16” port using the existing 5/16” valve core removal tool mounted to the port. Make sure that air is not introduced to the refrigerant charge so purge the small amount of air inside the valve core removal tool before screwing in the valve core. Test for a leak at the back of the valve core removal tool before removing the tool by applying “Big Blu” bubble leak detector https://amzn.to/3kZTuXC to the end of the tool to see if any bubbles form. If no bubble form, remove the tool and place a cap on the port. Step 39. Seal the hole through the exterior wall and around the tubing, cable, and condensate line so that rain does not enter the wall of the building. This can be done with exterior sealant such as Geocell tri-polymer sealant https://amzn.to/2G33ccN. Step 40. Add a cover over the line set, cable, and condensate line such as Mini-Split Slim-Duct casing or by using a plastic downspout. To install the downspout, cut the back of the spout down the length of it. Add a 60-degree elbow at the top and cut that elbow on an angle so it looks like it is penetrating through the siding but really it is just sitting flush against it. Either that or run the downspout up to the bottom of the soffit. Use several two-hole plastic or aluminum straps to secure the downspout over the tubes on the wall. Use stainless steel screws to secure the straps so that the screws do not rust and stain the siding. Step 41. Run the electrical cabling down along with the line set tubes and lightly zip tie them in place. Run the electrical cabling into the outdoor unit’s electrical panel and mount it in place with the appropriate connector. Step 42. To connect the four cables to the outdoor unit, cut them each to length, strip them, and add crimp connectors to the end of each stranded wire. Place each connector under the appropriate mounting screw to line up the color wire with the designated terminals A, B, C or 1, 2, 3 like at the indoor head unit terminals. Tighten each connector in place, including the ground. Step 43. To connect the 240-volt power wires, dry fit flexible conduit in place from the bottom of the disconnect box to the outdoor unit and cut it to length. Fish the three THWN coated stranded wires through the flexible conduit with an extra foot of length on each side of the conduit. Cut the wires. Add the connectors to the ends of the flexible conduit. Mount the conduit to both the outdoor disconnect and to the outdoor Mini-Split unit so that the wires are in each location. Connect the power wires and ground wire to the lugs inside the disconnect. Connect the power wires and ground to the outdoor Mini-Split unit. Put the electrical covers on both the electrical disconnect and the outdoor Mini-Split Unit. Step 44. You are ready to turn the power on. Remove the disconnect plug at the outdoor disconnect box and turn the indoor building breaker to the on position. Test for the correct power at the outdoor disconnect with a multimeter. When ready, insert the disconnect to turn the system on. Set the indoor thermostat to the desired mode and enjoy the comfort of the system! If you are an HVACR tech and this is not your home, hurry up, clean up, and get on to your next job! People always say it must be nice to work on air conditioning in the summer. I reply with, not really because as soon as you get the AC on, you need to leave and go to the next job where the AC is broke! Remember that you must be EPA 608 Certified before buying or handling refrigerants per EPA 608 law. If you want to learn more about refrigerants and how they work in a system, check out our “Refrigerant Charging and Service Procedures for Air Conditioning” book at https://www.acservicetech.com/ac-book. Test your knowledge with our 1,000 question workbook along with the answer key! We also have quick reference cards for use out in the field! Bundle Packs are a great way to save and get faster shipping! Check out our other article on checking the refrigerant charge of a Mini-Split unit! https://www.acservicetech.com/post/checking-the-charge-of-a-mini-split-unit Check out our free Quizzes to test your knowledge here! Check out our Free Calculators here! Tools that we use: www.amazon.com/shop/acservicetech Follow us on Facebook for Quick Tips and Updates here! Published: 11/25/2020 Author: Craig Migliaccio About the Author: Craig is the owner of AC Service Tech LLC and the Author of the book “Refrigerant Charging and Service Procedures for Air Conditioning”. Craig is a licensed Teacher of HVACR, Sheet Metal, and Building Maintenance in the State of New Jersey of the USA. He is also an HVACR Contracting Business owner of 15 years and holds an NJ HVACR Master License. Craig creates educational HVACR articles and videos which are posted at https://www.acservicetech.com & https://www.youtube.com/acservicetechchannel & https://www.facebook.com/acservicetech/